Can belt drive inline axial and centrifugal fans be mounted with the motors at 3 or 9 o'clock?
Link text :
Select a Card/Question Answer :
QuestionAnswer
Display order :
2
Yes. Greenheck's inline axial and centrifugal fan Models RA and BSQ-M are very versatile in mounting. However, keep in mind when mounting the fan with the motor on the side, the motor weight may cause uneven loading on the isolators. Overcome this uneven loading by mounting the fan on a set of rails that extend beyond the fan on both sides so that the weight of the fan and motor is between the outboard isolators.