What is the "damper location" under the configuration tab in CAPS?
Link text :
Select a Card/Question Answer : QuestionAnswer
Display order : 14
The damper location for all multi-blade models (FSD, SMD, VCD and DFD-210 series) is referred to as the A dimension (distance from end of sleeve to face of damper). The minimum space allowed is 182.575 millimeters (7.188 inches) and is the default in CAPS. The damper location for curtain style fire dampers (FD and DFD) is referred to as the K dimension (distance from end of sleeve to centerline of damper frame).